Skip to main content

CVE-2021-31895: CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') in Siemens RUGGEDCOM i800

High
VulnerabilityCVE-2021-31895cvecve-2021-31895cwe-120
Published: Tue Jul 13 2021 (07/13/2021, 11:02:59 UTC)
Source: CVE
Vendor/Project: Siemens
Product: RUGGEDCOM i800

Description

A vulnerability has been identified in RUGGEDCOM i800 (All versions < V4.3.7), RUGGEDCOM i801 (All versions < V4.3.7), RUGGEDCOM i802 (All versions < V4.3.7), RUGGEDCOM i803 (All versions < V4.3.7), RUGGEDCOM M2100 (All versions < V4.3.7), RUGGEDCOM M2200 (All versions < V4.3.7), RUGGEDCOM M969 (All versions < V4.3.7), RUGGEDCOM RMC30 (All versions < V4.3.7), RUGGEDCOM RMC8388 V4.X (All versions < V4.3.7), RUGGEDCOM RMC8388 V5.X (All versions < V5.5.4), RUGGEDCOM RP110 (All versions < V4.3.7), RUGGEDCOM RS1600 (All versions < V4.3.7), RUGGEDCOM RS1600F (All versions < V4.3.7), RUGGEDCOM RS1600T (All versions < V4.3.7), RUGGEDCOM RS400 (All versions < V4.3.7), RUGGEDCOM RS401 (All versions < V4.3.7), RUGGEDCOM RS416 (All versions < V4.3.7), RUGGEDCOM RS416P (All versions < V4.3.7), RUGGEDCOM RS416Pv2 V4.X (All versions < V4.3.7), RUGGEDCOM RS416Pv2 V5.X (All versions < V5.5.4), RUGGEDCOM RS416v2 V4.X (All versions < V4.3.7), RUGGEDCOM RS416v2 V5.X (All versions < 5.5.4), RUGGEDCOM RS8000 (All versions < V4.3.7), RUGGEDCOM RS8000A (All versions < V4.3.7), RUGGEDCOM RS8000H (All versions < V4.3.7), RUGGEDCOM RS8000T (All versions < V4.3.7), RUGGEDCOM RS900 (32M) V4.X (All versions < V4.3.7), RUGGEDCOM RS900 (32M) V5.X (All versions < V5.5.4), RUGGEDCOM RS900G (All versions < V4.3.7), RUGGEDCOM RS900G (32M) V4.X (All versions < V4.3.7), RUGGEDCOM RS900G (32M) V5.X (All versions < V5.5.4), RUGGEDCOM RS900GP (All versions < V4.3.7), RUGGEDCOM RS900L (All versions < V4.3.7), RUGGEDCOM RS900W (All versions < V4.3.7), RUGGEDCOM RS910 (All versions < V4.3.7), RUGGEDCOM RS910L (All versions < V4.3.7), RUGGEDCOM RS910W (All versions < V4.3.7), RUGGEDCOM RS920L (All versions < V4.3.7), RUGGEDCOM RS920W (All versions < V4.3.7), RUGGEDCOM RS930L (All versions < V4.3.7), RUGGEDCOM RS930W (All versions < V4.3.7), RUGGEDCOM RS940G (All versions < V4.3.7), RUGGEDCOM RS969 (All versions < V4.3.7), RUGGEDCOM RSG2100 (All versions), RUGGEDCOM RSG2100 (32M) V4.X (All versions < V4.3.7), RUGGEDCOM RSG2100 (32M) V5.X (All versions < V5.5.4), RUGGEDCOM RSG2100P (All versions < V4.3.7), RUGGEDCOM RSG2100P (32M) V4.X (All versions < V4.3.7), RUGGEDCOM RSG2100P (32M) V5.X (All versions < V5.5.4), RUGGEDCOM RSG2100PNC (32M) V4.X (All versions < V4.3.7), RUGGEDCOM RSG2100PNC (32M) V5.X (All versions < V5.5.4), RUGGEDCOM RSG2200 (All versions < V4.3.7), RUGGEDCOM RSG2288 V4.X (All versions < V4.3.7), RUGGEDCOM RSG2288 V5.X (All versions < V5.5.4), RUGGEDCOM RSG2300 V4.X (All versions < V4.3.7), RUGGEDCOM RSG2300 V5.X (All versions < V5.5.4), RUGGEDCOM RSG2300P V4.X (All versions < V4.3.7), RUGGEDCOM RSG2300P V5.X (All versions < V5.5.4), RUGGEDCOM RSG2488 V4.X (All versions < V4.3.7), RUGGEDCOM RSG2488 V5.X (All versions < V5.5.4), RUGGEDCOM RSG907R (All versions < V5.5.4), RUGGEDCOM RSG908C (All versions < V5.5.4), RUGGEDCOM RSG909R (All versions < V5.5.4), RUGGEDCOM RSG910C (All versions < V5.5.4), RUGGEDCOM RSG920P V4.X (All versions < V4.3.7), RUGGEDCOM RSG920P V5.X (All versions < V5.5.4), RUGGEDCOM RSL910 (All versions < V5.5.4), RUGGEDCOM RST2228 (All versions < V5.5.4), RUGGEDCOM RST2228P (All versions < V5.5.4), RUGGEDCOM RST916C (All versions < V5.5.4), RUGGEDCOM RST916P (All versions < V5.5.4). The DHCP client in affected devices fails to properly sanitize incoming DHCP packets. This could allow an unauthenticated remote attacker to cause memory to be overwritten, potentially allowing remote code execution.

AI-Powered Analysis

AILast updated: 07/04/2025, 21:25:07 UTC

Technical Analysis

CVE-2021-31895 is a high-severity buffer overflow vulnerability affecting multiple Siemens RUGGEDCOM devices, including the i800 series and numerous related models, with all versions prior to V4.3.7 (or V5.5.4 for some variants) being vulnerable. The root cause is a classic buffer overflow (CWE-120) in the DHCP client implementation of these devices. Specifically, the DHCP client fails to properly sanitize incoming DHCP packets, allowing an unauthenticated remote attacker to send specially crafted DHCP packets that overwrite memory. This memory corruption can lead to remote code execution (RCE) on the affected device. The vulnerability is remotely exploitable over the network without requiring authentication or user interaction, though the attack complexity is rated as high due to the need for crafting precise packets. The CVSS v3.1 base score is 8.1, reflecting high impact on confidentiality, integrity, and availability, with remote network attack vector and no privileges required. Siemens RUGGEDCOM devices are ruggedized industrial network components widely used in critical infrastructure sectors such as energy, transportation, and utilities. The affected devices include routers, switches, and other network appliances designed for harsh environments. Exploitation could allow attackers to gain full control of these devices, disrupt network operations, intercept or manipulate data, and potentially pivot into industrial control systems. No known exploits in the wild have been reported, but the vulnerability's nature and affected product profile make it a significant threat to operational technology (OT) environments. Siemens has released firmware updates (V4.3.7 or V5.5.4 and later) that address this issue by properly sanitizing DHCP packets to prevent buffer overflow.

Potential Impact

For European organizations, especially those operating critical infrastructure such as energy grids, transportation networks, and industrial facilities, this vulnerability poses a serious risk. Siemens RUGGEDCOM devices are commonly deployed in these sectors across Europe due to their ruggedness and reliability in harsh environments. Successful exploitation could lead to remote code execution, allowing attackers to disrupt network communications, cause denial of service, or manipulate control data, potentially leading to operational outages or safety incidents. Confidentiality breaches could expose sensitive operational data, while integrity violations could result in malicious command injection or falsified telemetry. The availability of critical network components could be compromised, affecting service continuity. Given the strategic importance of energy and transportation infrastructure in Europe, exploitation could have cascading effects on national security and public safety. The vulnerability's remote and unauthenticated nature increases the risk, especially if devices are exposed to untrusted networks or insufficiently segmented environments. Organizations in Europe must prioritize patching and network segmentation to mitigate potential impacts.

Mitigation Recommendations

1. Immediate firmware upgrade: Organizations should promptly update all affected Siemens RUGGEDCOM devices to the fixed versions (V4.3.7 or V5.5.4 and later) provided by Siemens. This is the most effective mitigation to eliminate the vulnerability. 2. Network segmentation: Isolate RUGGEDCOM devices within dedicated network segments with strict access controls to limit exposure to untrusted networks and reduce attack surface. 3. DHCP traffic filtering: Implement network-level filtering to restrict DHCP traffic to trusted sources only, preventing malicious DHCP packets from reaching vulnerable devices. 4. Intrusion detection and monitoring: Deploy network intrusion detection systems (NIDS) with signatures or anomaly detection tuned to identify suspicious DHCP traffic patterns targeting these devices. 5. Access control hardening: Restrict management interfaces and protocols to authorized personnel and systems, and disable unused services to reduce potential exploitation vectors. 6. Incident response readiness: Prepare for potential exploitation by establishing monitoring and response procedures specific to industrial network devices, including logging and forensic capabilities. 7. Vendor coordination: Maintain communication with Siemens for updates, advisories, and support related to this vulnerability and other emerging threats.

Need more detailed analysis?Get Pro

Technical Details

Data Version
5.1
Assigner Short Name
siemens
Date Reserved
2021-04-29T00:00:00
Cisa Enriched
false
Cvss Version
3.1
State
PUBLISHED

Threat ID: 682d9816c4522896dcbd6686

Added to database: 5/21/2025, 9:08:38 AM

Last enriched: 7/4/2025, 9:25:07 PM

Last updated: 8/2/2025, 12:27:29 AM

Views: 14

Actions

PRO

Updates to AI analysis are available only with a Pro account. Contact root@offseq.com for access.

Please log in to the Console to use AI analysis features.

Need enhanced features?

Contact root@offseq.com for Pro access with improved analysis and higher rate limits.