A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.10), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants) (All versions < V10.1), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions < V8.2.3), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Affected devices improperly handle specially crafted packets sent to port 102/tcp. This could allow an attacker to create a Denial-of-Service condition. A restart is needed to restore normal operations.

AI-Powered Analysis

AILast updated: 06/20/2025, 13:48:29 UTC

Technical Analysis

CVE-2021-40368 is a medium-severity vulnerability affecting multiple versions of Siemens SIMATIC S7-400 series CPUs, including models 412-1 DP V7, 412-2 DP V7, 414-2 DP V7, 414-3 DP V7, 416-2 DP V7, 416-3 DP V7, 417-4 DP V7, and their SIPLUS variants, among others. The vulnerability arises from improper restriction of operations within the bounds of a memory buffer (CWE-119). Specifically, these devices improperly handle specially crafted packets sent to TCP port 102, which is typically used for the ISO-on-TCP protocol (also known as RFC 1006), a common communication protocol in industrial control systems (ICS) for Siemens PLCs. An attacker sending maliciously crafted packets to this port can trigger a buffer overflow or similar memory corruption condition, leading to a Denial-of-Service (DoS) state. This DoS condition causes the affected CPU to become unresponsive or malfunction, requiring a manual restart to restore normal operations. The vulnerability affects all versions of the listed products prior to certain fixed versions (e.g., V7.0.3 for some models, V6.0.10 for others), and no public exploits or active exploitation in the wild have been reported to date. However, the vulnerability's nature makes it a significant risk in industrial environments where availability and reliability are critical. The attack vector is network-based and does not require authentication, but it does require the attacker to have network access to the device's TCP port 102, which is often exposed within industrial networks or via remote access solutions. Given the critical role of SIMATIC S7-400 CPUs in controlling industrial processes, this vulnerability could disrupt manufacturing, energy production, or infrastructure operations if exploited.

Potential Impact

For European organizations, particularly those in manufacturing, energy, utilities, transportation, and critical infrastructure sectors, this vulnerability poses a risk of operational disruption. Exploitation can cause a denial-of-service condition on PLCs that manage essential industrial processes, potentially halting production lines, causing safety system failures, or interrupting critical services. The need for a manual restart to recover can lead to prolonged downtime and increased operational costs. Additionally, such disruptions could have cascading effects on supply chains and service delivery. Since Siemens SIMATIC S7-400 series PLCs are widely deployed across Europe, especially in Germany, France, Italy, and the UK, the impact could be significant in these countries. The vulnerability does not appear to allow code execution or data manipulation beyond causing a DoS, so confidentiality and integrity impacts are limited. However, availability impacts are high, which is critical in industrial control environments. The lack of known exploits reduces immediate risk, but the potential for targeted attacks or exploitation by threat actors with network access remains. Organizations with remote access to industrial networks or insufficient network segmentation are at higher risk.

Mitigation Recommendations

1. Apply Siemens' official firmware updates and patches as soon as they become available for the affected SIMATIC S7-400 CPU models. Siemens typically releases security advisories and patches addressing such vulnerabilities. 2. Implement strict network segmentation to isolate industrial control systems from corporate and external networks. Ensure that TCP port 102 is not exposed to untrusted networks or the internet. 3. Deploy network intrusion detection/prevention systems (IDS/IPS) with signatures or anomaly detection capabilities tuned for IEC 104/ISO-on-TCP traffic to detect and block malformed packets targeting port 102. 4. Restrict access to the industrial network using firewalls and VPNs with strong authentication and logging to prevent unauthorized access. 5. Monitor PLCs and industrial network traffic for unusual activity or repeated connection attempts to port 102 that could indicate scanning or exploitation attempts. 6. Develop and test incident response plans specifically for industrial control system DoS scenarios, including rapid restart procedures and fallback operations to minimize downtime. 7. Conduct regular security assessments and penetration testing focused on ICS environments to identify and remediate exposure of vulnerable devices. 8. Educate operational technology (OT) personnel about this vulnerability and the importance of maintaining up-to-date firmware and network hygiene.

Need more detailed analysis?Get Pro

Technical Details

Data Version
5.1
Assigner Short Name
siemens
Date Reserved
2021-09-01T00:00:00.000Z
Cisa Enriched
true

Threat ID: 682d984bc4522896dcbf7f32

Added to database: 5/21/2025, 9:09:31 AM

Last enriched: 6/20/2025, 1:48:29 PM

Last updated: 8/12/2025, 3:34:00 PM