CVE-2022-26647: CWE-330: Use of Insufficiently Random Values in Siemens SCALANCE X200-4P IRT

Medium
Published: Tue Jul 12 2022 (07/12/2022, 10:06:32 UTC)
Source: CVE
Vendor/Project: Siemens
Product: SCALANCE X200-4P IRT

Description

A vulnerability has been identified in SCALANCE X200-4P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT (All versions < V5.5.2), SCALANCE X201-3P IRT PRO (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2IRT (All versions < V5.5.2), SCALANCE X202-2P IRT (All versions < V5.5.2), SCALANCE X202-2P IRT PRO (All versions < V5.5.2), SCALANCE X204-2 (All versions < V5.2.6), SCALANCE X204-2FM (All versions < V5.2.6), SCALANCE X204-2LD (All versions < V5.2.6), SCALANCE X204-2LD TS (All versions < V5.2.6), SCALANCE X204-2TS (All versions < V5.2.6), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT (All versions < V5.5.2), SCALANCE X204IRT PRO (All versions < V5.5.2), SCALANCE X206-1 (All versions < V5.2.6), SCALANCE X206-1LD (All versions < V5.2.6), SCALANCE X208 (All versions < V5.2.6), SCALANCE X208PRO (All versions < V5.2.6), SCALANCE X212-2 (All versions < V5.2.6), SCALANCE X212-2LD (All versions < V5.2.6), SCALANCE X216 (All versions < V5.2.6), SCALANCE X224 (All versions < V5.2.6), SCALANCE XF201-3P IRT (All versions < V5.5.2), SCALANCE XF202-2P IRT (All versions < V5.5.2), SCALANCE XF204 (All versions < V5.2.6), SCALANCE XF204-2 (All versions < V5.2.6), SCALANCE XF204-2BA IRT (All versions < V5.5.2), SCALANCE XF204IRT (All versions < V5.5.2), SCALANCE XF206-1 (All versions < V5.2.6), SCALANCE XF208 (All versions < V5.2.6). The webserver of affected devices calculates session ids and nonces in an insecure manner. This could allow an unauthenticated remote attacker to brute-force session ids and hijack existing sessions.

AI-Powered Analysis

AILast updated: 06/20/2025, 13:04:07 UTC

Technical Analysis

CVE-2022-26647 is a vulnerability affecting multiple Siemens SCALANCE industrial network devices, specifically models in the X200 and XF200 series, including variants such as X200-4P IRT, X201-3P IRT, X202-2IRT, X204-2, X206-1, X208, X212-2, X216, X224, XF201-3P IRT, XF202-2P IRT, XF204, XF206-1, and XF208. All versions prior to V5.5.2 or V5.2.6 depending on the model are affected. The root cause is the use of insufficiently random values in the generation of session identifiers and nonces by the embedded webserver on these devices. This weakness falls under CWE-330, which relates to the use of predictable or insufficiently random values in security-critical contexts. Because session IDs and nonces are used to maintain and validate authenticated sessions, their predictability enables an unauthenticated remote attacker to brute-force these values. Successfully guessing a valid session ID would allow the attacker to hijack an existing session, potentially gaining unauthorized access to the device's management interface. This could lead to unauthorized configuration changes, disruption of network communications, or further pivoting into industrial control networks. The vulnerability does not require authentication or user interaction, and no known exploits are currently reported in the wild. However, the affected devices are widely deployed in industrial environments for critical infrastructure and manufacturing automation, making them high-value targets. Siemens has released firmware updates (V5.5.2 or V5.2.6 and later) that address this issue by improving the randomness of session tokens. The vulnerability was publicly disclosed in July 2022, and while no CVSS score is assigned, the medium severity rating reflects the moderate risk posed by session hijacking through brute force due to insufficient entropy in session identifiers.

Potential Impact

For European organizations, especially those operating in manufacturing, energy, transportation, and critical infrastructure sectors, this vulnerability poses a significant risk. Siemens SCALANCE devices are commonly used in industrial Ethernet networks to ensure real-time communication and network segmentation. Exploitation could allow attackers to gain unauthorized access to network management interfaces, leading to potential manipulation or disruption of industrial processes. This could result in operational downtime, safety hazards, data integrity issues, and financial losses. Given the critical role these devices play in industrial control systems (ICS) and operational technology (OT) environments, successful exploitation could also facilitate lateral movement to other sensitive systems. The impact is heightened in sectors subject to strict regulatory requirements such as the EU NIS Directive, where security incidents can lead to legal and reputational consequences. Although no active exploitation has been reported, the ease of brute forcing weak session IDs without authentication increases the attack surface, especially if devices are exposed to untrusted networks or insufficiently segmented environments.

Mitigation Recommendations

1. Immediate firmware upgrade: Organizations should prioritize updating all affected Siemens SCALANCE devices to the latest firmware versions (V5.5.2 or V5.2.6 and above) provided by Siemens, which implement stronger randomness in session ID generation. 2. Network segmentation: Ensure that management interfaces of SCALANCE devices are isolated from general enterprise networks and internet exposure. Use VLANs, firewalls, and access control lists to restrict access only to authorized personnel and systems. 3. Implement strong authentication: Where possible, enable multi-factor authentication (MFA) or integrate device management with centralized authentication systems to reduce the risk of unauthorized access even if session hijacking occurs. 4. Monitor network traffic: Deploy intrusion detection/prevention systems (IDS/IPS) tuned to detect anomalous session ID brute force attempts or unusual access patterns to the device management interfaces. 5. Limit session lifetime and enforce session timeouts to reduce the window of opportunity for session hijacking. 6. Conduct regular security audits and vulnerability assessments on industrial network devices to identify outdated firmware and configuration weaknesses. 7. Educate OT and IT staff on the risks of exposing industrial device management interfaces and the importance of timely patching and network hygiene.

Need more detailed analysis?Get Pro

Technical Details

Data Version
5.1
Assigner Short Name
siemens
Date Reserved
2022-03-07T00:00:00.000Z
Cisa Enriched
true

Threat ID: 682d984bc4522896dcbf8032

Added to database: 5/21/2025, 9:09:31 AM

Last enriched: 6/20/2025, 1:04:07 PM

Last updated: 8/18/2025, 3:43:45 AM

Views: 16

Actions

PRO

Updates to AI analysis are available only with a Pro account. Contact root@offseq.com for access.

Please log in to the Console to use AI analysis features.

Need enhanced features?

Contact root@offseq.com for Pro access with improved analysis and higher rate limits.

Latest Threats