CVE-2026-58114: Siemens SIMATIC BATCH V9.1 · Weak Authentication
Affects Siemens SIMATIC BATCH V9.1Source CVE Database V5
Not known to be exploited · CVSS 7.5 High.
Data as of 10 Nov 2026, 11:49 UTC
Thin evidence
One scorer or none| CNA (siemens) | CVSS 3.1 | 7.5 |
|---|---|---|
| CNA (siemens) | CVSS 4.0 | 7.7 |
CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:HExploitation evidence
Disclosed: evidence found.
CVE published 10 Nov 2026
Detectable: no evidence on record.
No public nuclei template indexed
Weaponized: no evidence on record.
No public exploit code indexed in Metasploit or Exploit-DB
Exploited in the wildExploited: no evidence on record.
Not in CISA KEV and no source reports exploitation
Observed by OffSeq MirageSeen by Mirage: no evidence on record.
No attack traffic recorded by OffSeq Mirage sensors
A missing step is not evidence of safety. Sources: cve.org (opens in a new tab), the Metasploit, Exploit-DB and nuclei-templates index as of 10 Nov 2026.
What to do
Affected software
| Product | Affected | Fixed in |
|---|---|---|
| SiemensSIMATIC BATCH V9.1 | Affected
| Fixed in– |
| SiemensSIMATIC Information Server 2020 | Affected
| Fixed in– |
| SiemensSIMATIC Information Server 2022 | Affected
| Fixed in– |
| SiemensSIMATIC PCS 7 V9.1 | Affected
| Fixed in– |
| SiemensSIMATIC Process Historian 2020 | Affected
| Fixed in– |
| SiemensSIMATIC Process Historian 2022 | Affected
| Fixed in– |
AI-suggested
No specific patch or remediation is currently provided in the available data. Since the vulnerability stems from the use of the deprecated NTLM protocol, mitigation may involve disabling NTLM authentication where possible and migrating to more secure authentication protocols. Monitor Siemens advisories for official fixes or guidance. Until a patch is available, restrict network access to affected services and use network-level protections to prevent man-in-the-middle attacks.
Description
CVE-2026-58114 is a high-severity vulnerability affecting multiple Siemens SIMATIC products including SIMATIC BATCH V9.1 and various versions of SIMATIC Information Server, PCS 7, Process Historian, and WinCC Runtime Professional. The issue arises from the use of the deprecated NTLM protocol for remote user authentication, which does not properly secure authentication. This flaw allows unauthenticated remote attackers positioned as a man-in-the-middle to relay NTLM authentication and impersonate legitimate users. The impact depends on accessible services, such as SQL servers used by WinCC.