Skip to main content
VulnerabilityPublished

CVE-2026-58115: SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All · Missing Authentication

Source GCVE Database

0
Compare
Authoritative record:CVE-2026-58115· Critical 10.0

Not known to be exploited · CVSS 10.0 Critical : upgrade to 4.3.4-1 as a priority.

Data as of 9 Nov 2026, 23:24 UTC

CVSS 3.1 base score
10.0Critical
How severe the flaw is on the 0–10 CVSS scale.

Thin evidence

One scorer or none
CVSS scores by source
CNA (siemens)CVSS 3.110.0
CNA (siemens)CVSS 4.010.0
EPSS
0.8% chance of exploitation in 30 days – higher than 59% of CVEsExploit Prediction Scoring System: the likelihood attackers will use this flaw soon.
Patch
Available – fixed in 4.3.4-1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

Exploitation evidence

  1. Disclosed: evidence found.

    CVE published 11 Aug 2026

  2. Detectable: no evidence on record.

    No public nuclei template indexed

  3. Weaponized: no evidence on record.

    No public exploit code indexed in Metasploit or Exploit-DB

  4. Exploited in the wild: no evidence on record.

    Not in CISA KEV and no source reports exploitation

  5. Observed by OffSeq Mirage: no evidence on record.

    No attack traffic recorded by OffSeq Mirage sensors

A missing step is not evidence of safety. Sources: cve.org (opens in a new tab), the Metasploit, Exploit-DB and nuclei-templates index as of 9 Nov 2026.

What to do

Upgrade SIMATIC IoT2050 to 4.3.4-1.

Affected software

ProductAffectedFixed in
SiemensSIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2)Affected
  • <4.3.4-1
Fixed in
  • 4.3.4-1
SiemensSIMATIC IoT2050 Basic (6ES7647-0BA00-0YA2)Affected
  • <4.3.4-1
Fixed in
  • 4.3.4-1
SiemensSIMATIC IoT2050 M.2 (6ES7647-0BB00-1YA2)Affected
  • <4.3.4-1
Fixed in
  • 4.3.4-1
SiemensSIMATIC IoT2050 SM (6ES7647-0CA00-1AA2)Affected
  • <4.3.4-1
Fixed in
  • 4.3.4-1

AI-suggested

If you cannot patch yet, restrict network access to the Node-RED HTTP interface to trusted users only and consider disabling Node-RED if not required.

Description

A critical vulnerability exists in SIMATIC IoT2050 Advanced devices running Industrial OS with Node-RED installed, affecting all versions prior to V4.3.4.1. The issue arises because the Node-RED HTTP interface does not enforce authentication, allowing unauthenticated remote attackers to access programming nodes. This access enables attackers to create malicious flows that execute arbitrary system commands with maximum privileges on the underlying server.