CVE-2024-57811: Eaton X303 · Use of Hard-coded Credentials
Source CVE Database V5
Not known to be exploited · CVSS 9.1 Critical · end of life, no fix coming : replace or isolate affected systems; no fix will be released.
Data as of 26 Oct 2026, 17:16 UTC
- EPSS
- 0.4% chance of exploitation in 30 days – higher than 38% of CVEsExploit Prediction Scoring System: the likelihood attackers will use this flaw soon.
- Patch
- None coming – the product is end of life
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:HExploitation evidence
Disclosed: evidence found.
CVE published 13 Jan 2025
Detectable: no evidence on record.
No public nuclei template indexed
Weaponised: no evidence on record.
No public exploit code indexed in Metasploit or Exploit-DB
Exploited in the wildExploited: no evidence on record.
Not in CISA KEV and no source reports exploitation
Observed by OffSeq MirageSeen by Mirage: no evidence on record.
No attack traffic recorded by OffSeq Mirage sensors
A missing step is not evidence of safety. Sources: cve.org (opens in a new tab), the Metasploit, Exploit-DB and nuclei-templates index as of 26 Oct 2026.
What to do
No fix will be released: the affected product is end of life. Replace it, or isolate it from untrusted networks until you can.
AI-suggested
Since no patches or firmware updates are available for the affected Eaton XC-303 PLC versions, organizations must implement compensating controls to mitigate risk. First, immediately identify and inventory all affected PLCs within the network. Restrict network access to these devices by implementing strict network segmentation and firewall rules, allowing SSH access only from trusted management stations or isolated networks. Disable or block SSH access if it is not essential for operations. Employ network intrusion detection systems (NIDS) to monitor for suspicious SSH login attempts or unusual traffic patterns targeting PLCs. Consider deploying jump servers or bastion hosts with multi-factor authentication to control administrative access. If feasible, replace affected PLCs with updated or alternative devices that do not contain hardcoded credentials. Conduct regular security assessments and penetration tests focused on OT environments to detect potential exploitation attempts. Finally, develop and rehearse incident response plans specific to OT systems to quickly contain and remediate any compromise involving these PLCs.
Description
In Eaton X303 3.5.16 - X303 3.5.17 Build 712, an attacker with network access to a XC-303 PLC can login as root over SSH. The root password is hardcoded in the firmware. NOTE: This vulnerability appears in versions that are no longer supported by Eaton.