CVE-2026-105281: Grid Protection Alliance openPDC · Missing Authentication

Affects Grid Protection Alliance openPDCSource CVE Database V5

0
Compare

Not known to be exploited · CVSS 7.5 High : upgrade to 2.9.482 or 2.9.477 soon.

Data as of 15 Nov 2026, 20:25 UTC

CVSS 3.1 base score
7.5High
How severe the flaw is on the 0–10 CVSS scale.
EPSS
0.3% chance of exploitation in 30 days – higher than 24% of CVEsExploit Prediction Scoring System: the likelihood attackers will use this flaw soon.
Patch
Available – fixed in 2.9.482, 2.9.477, 2.8.585 +1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Exploitation evidence

  1. Disclosed: evidence found.

    CVE published 9 Oct 2026

  2. Detectable: no evidence on record.

    No public nuclei template indexed

  3. Weaponized: no evidence on record.

    No public exploit code indexed in Metasploit or Exploit-DB

  4. Exploited in the wild: no evidence on record.

    Not in CISA KEV and no source reports exploitation

  5. Observed by OffSeq Mirage: no evidence on record.

    No attack traffic recorded by OffSeq Mirage sensors

A missing step is not evidence of safety. Sources: cve.org (opens in a new tab), the Metasploit, Exploit-DB and nuclei-templates index as of 15 Nov 2026.

What to do

Upgrade openPDC and openPDC (Docker image) to 2.9.482 or 2.9.477; openHistorian to 2.8.585 or 2.8.580.

Affected software

ProductAffectedFixed in
Grid Protection AllianceopenPDCAffected
  • <2.9.482
Fixed in
  • 2.9.482
Grid Protection AllianceopenPDCAffected
  • <2.9.477
Fixed in
  • 2.9.477
Grid Protection AllianceopenPDC (Docker image)Affected
  • <2.9.482
Fixed in
  • 2.9.482
Grid Protection AllianceopenPDC (Docker image)Affected
  • <2.9.477
Fixed in
  • 2.9.477
Grid Protection AllianceopenHistorianAffected
  • <2.8.585
Fixed in
  • 2.8.585
Grid Protection AllianceopenHistorianAffected
  • <2.8.580
Fixed in
  • 2.8.580

AI-suggested

If you cannot patch yet, restrict network access to the internal data publisher interface to trusted hosts only or apply network-level controls to prevent unauthorized connections.

Description

CVE-2026-105281 is a vulnerability in the Grid Protection Alliance openPDC product where the internal data publisher accepts network connections without authentication by default. This allows an unauthenticated attacker to connect remotely and retrieve the full device and measurement topology of the system. The vulnerability affects multiple versions prior to 2.9.477, 2.9.482, 2.8.580, and 2.8.585. The CVSS 3.1 base score is 7.5, indicating high severity due to the ability to obtain sensitive configuration information without privileges.