CVE-2024-22040: CWE-125: Out-of-bounds Read in Siemens Cerberus PRO EN Engineering Tool
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread. This could allow an unauthenticated remote attacker to crash the network service.
AI Analysis
Technical Summary
CVE-2024-22040 is an out-of-bounds read vulnerability classified under CWE-125 affecting multiple Siemens fire safety and engineering products, including Cerberus PRO EN Engineering Tool, various Cerberus PRO EN Fire Panels (FC72x IP6, IP7, IP8), X200 and X300 Cloud Distribution systems, UL Compact Panels, Desigo Fire Safety UL products, Sinteso FS20 EN Engineering Tools, Fire Panels, Cloud Distributions, and Sinteso Mobile. The root cause is insufficient validation of HMAC values within the network communication library, which leads to a buffer overread condition. This vulnerability can be triggered remotely by an unauthenticated attacker sending specially crafted network packets, causing the affected service to crash, resulting in denial of service. The CVSS v3.1 score is 7.5 (high), reflecting the network attack vector, lack of required privileges or user interaction, and the impact limited to availability. The vulnerability does not compromise confidentiality or integrity but can disrupt critical fire safety monitoring and control systems. No public exploits have been reported yet, but the affected products are widely used in safety-critical environments, increasing the urgency for remediation. Siemens has not yet published patches for all affected versions, so organizations should monitor vendor advisories closely. The vulnerability affects all versions of some products and specific versions below certain service releases for others, indicating the need for version-specific mitigation strategies.
Potential Impact
The primary impact of CVE-2024-22040 is denial of service through crashing of network services in fire safety and engineering tools. For European organizations, this could disrupt fire detection, alarm, and suppression systems, potentially delaying emergency responses and increasing safety risks in industrial, commercial, and critical infrastructure environments. The availability impact is significant given the safety-critical nature of these systems. While confidentiality and integrity are not directly affected, the loss of availability in fire safety systems can have severe operational and regulatory consequences, including non-compliance with safety standards and potential legal liabilities. Organizations in sectors such as manufacturing, energy, transportation, healthcare, and public administration that deploy Siemens Cerberus and Sinteso products are at heightened risk. The remote and unauthenticated nature of the exploit increases the threat level, as attackers do not need internal access or user interaction. This vulnerability could also be leveraged as part of a broader attack chain targeting industrial control systems or building management systems, amplifying its impact.
Mitigation Recommendations
1. Immediate mitigation should focus on network-level controls: restrict access to the affected Siemens fire safety and engineering devices to trusted networks only, using firewalls and network segmentation to isolate these systems from untrusted or public networks. 2. Monitor network traffic for anomalous packets targeting the affected services, employing intrusion detection/prevention systems (IDS/IPS) with updated signatures if available. 3. Apply vendor patches and updates as soon as Siemens releases them for all affected products and versions; maintain an inventory of deployed versions to prioritize patching. 4. If patches are not yet available, consider temporary workarounds such as disabling vulnerable network services or applying rate limiting to reduce exposure to malformed packets. 5. Conduct regular security assessments and penetration testing focused on industrial and building management systems to identify and remediate similar vulnerabilities. 6. Maintain robust incident response plans that include scenarios involving denial-of-service attacks on safety-critical systems. 7. Engage with Siemens support and subscribe to their security advisories to receive timely updates and guidance. 8. Train operational technology (OT) staff on the risks and detection of such vulnerabilities to improve early identification and response.
Affected Countries
Germany, France, Italy, United Kingdom, Netherlands, Belgium, Switzerland, Austria, Spain, Sweden
CVE-2024-22040: CWE-125: Out-of-bounds Read in Siemens Cerberus PRO EN Engineering Tool
Description
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread. This could allow an unauthenticated remote attacker to crash the network service.
AI-Powered Analysis
Technical Analysis
CVE-2024-22040 is an out-of-bounds read vulnerability classified under CWE-125 affecting multiple Siemens fire safety and engineering products, including Cerberus PRO EN Engineering Tool, various Cerberus PRO EN Fire Panels (FC72x IP6, IP7, IP8), X200 and X300 Cloud Distribution systems, UL Compact Panels, Desigo Fire Safety UL products, Sinteso FS20 EN Engineering Tools, Fire Panels, Cloud Distributions, and Sinteso Mobile. The root cause is insufficient validation of HMAC values within the network communication library, which leads to a buffer overread condition. This vulnerability can be triggered remotely by an unauthenticated attacker sending specially crafted network packets, causing the affected service to crash, resulting in denial of service. The CVSS v3.1 score is 7.5 (high), reflecting the network attack vector, lack of required privileges or user interaction, and the impact limited to availability. The vulnerability does not compromise confidentiality or integrity but can disrupt critical fire safety monitoring and control systems. No public exploits have been reported yet, but the affected products are widely used in safety-critical environments, increasing the urgency for remediation. Siemens has not yet published patches for all affected versions, so organizations should monitor vendor advisories closely. The vulnerability affects all versions of some products and specific versions below certain service releases for others, indicating the need for version-specific mitigation strategies.
Potential Impact
The primary impact of CVE-2024-22040 is denial of service through crashing of network services in fire safety and engineering tools. For European organizations, this could disrupt fire detection, alarm, and suppression systems, potentially delaying emergency responses and increasing safety risks in industrial, commercial, and critical infrastructure environments. The availability impact is significant given the safety-critical nature of these systems. While confidentiality and integrity are not directly affected, the loss of availability in fire safety systems can have severe operational and regulatory consequences, including non-compliance with safety standards and potential legal liabilities. Organizations in sectors such as manufacturing, energy, transportation, healthcare, and public administration that deploy Siemens Cerberus and Sinteso products are at heightened risk. The remote and unauthenticated nature of the exploit increases the threat level, as attackers do not need internal access or user interaction. This vulnerability could also be leveraged as part of a broader attack chain targeting industrial control systems or building management systems, amplifying its impact.
Mitigation Recommendations
1. Immediate mitigation should focus on network-level controls: restrict access to the affected Siemens fire safety and engineering devices to trusted networks only, using firewalls and network segmentation to isolate these systems from untrusted or public networks. 2. Monitor network traffic for anomalous packets targeting the affected services, employing intrusion detection/prevention systems (IDS/IPS) with updated signatures if available. 3. Apply vendor patches and updates as soon as Siemens releases them for all affected products and versions; maintain an inventory of deployed versions to prioritize patching. 4. If patches are not yet available, consider temporary workarounds such as disabling vulnerable network services or applying rate limiting to reduce exposure to malformed packets. 5. Conduct regular security assessments and penetration testing focused on industrial and building management systems to identify and remediate similar vulnerabilities. 6. Maintain robust incident response plans that include scenarios involving denial-of-service attacks on safety-critical systems. 7. Engage with Siemens support and subscribe to their security advisories to receive timely updates and guidance. 8. Train operational technology (OT) staff on the risks and detection of such vulnerabilities to improve early identification and response.
For access to advanced analysis and higher rate limits, contact root@offseq.com
Technical Details
- Data Version
- 5.2
- Assigner Short Name
- siemens
- Date Reserved
- 2024-01-04T13:24:07.552Z
- Cvss Version
- 3.1
- State
- PUBLISHED
Threat ID: 69418d789050fe8508ffbf57
Added to database: 12/16/2025, 4:48:56 PM
Last enriched: 12/16/2025, 5:00:55 PM
Last updated: 12/20/2025, 2:25:47 PM
Views: 8
Community Reviews
0 reviewsCrowdsource mitigation strategies, share intel context, and vote on the most helpful responses. Sign in to add your voice and help keep defenders ahead.
Want to contribute mitigation steps or threat intel context? Sign in or create an account to join the community discussion.
Related Threats
CVE-2025-7782: CWE-862 Missing Authorization in WP JobHunt
HighCVE-2025-7733: CWE-639 Authorization Bypass Through User-Controlled Key in WP JobHunt
MediumCVE-2025-14298: CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') in damian-gora FiboSearch – Ajax Search for WooCommerce
MediumCVE-2025-12492: CWE-200 Exposure of Sensitive Information to an Unauthorized Actor in ultimatemember Ultimate Member – User Profile, Registration, Login, Member Directory, Content Restriction & Membership Plugin
MediumCVE-2025-13619: CWE-269 Improper Privilege Management in CMSSuperHeroes Flex Store Users
CriticalActions
Updates to AI analysis require Pro Console access. Upgrade inside Console → Billing.
Need enhanced features?
Contact root@offseq.com for Pro access with improved analysis and higher rate limits.