Skip to main content
Press slash or control plus K to focus the search. Use the arrow keys to navigate results and press enter to open a threat.
Reconnecting to live updates…

CVE-2024-22040: CWE-125: Out-of-bounds Read in Siemens Cerberus PRO EN Engineering Tool

0
High
VulnerabilityCVE-2024-22040cvecve-2024-22040cwe-125
Published: Tue Mar 12 2024 (03/12/2024, 10:21:54 UTC)
Source: CVE Database V5
Vendor/Project: Siemens
Product: Cerberus PRO EN Engineering Tool

Description

A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread. This could allow an unauthenticated remote attacker to crash the network service.

AI-Powered Analysis

AILast updated: 12/23/2025, 17:13:30 UTC

Technical Analysis

CVE-2024-22040 is an out-of-bounds read vulnerability classified under CWE-125, discovered in Siemens Cerberus PRO EN Engineering Tool and a broad range of associated fire safety products including various Cerberus PRO EN Fire Panels (FC72x series), X200 and X300 Cloud Distribution systems, UL Compact Panels, and Sinteso FS20 EN series devices. The root cause is insufficient validation of HMAC (Hash-based Message Authentication Code) values within the network communication library. HMAC is typically used to verify message integrity and authenticity; however, in this case, improper validation leads to a buffer overread condition. This means that when processing network messages, the software reads beyond the allocated buffer boundaries, which can cause memory corruption or application crashes. The vulnerability can be triggered remotely by an unauthenticated attacker sending specially crafted network packets, requiring no user interaction or prior authentication. The primary impact is a denial of service (DoS) due to crashing the network service, potentially disrupting fire safety monitoring and control functions. The CVSS 3.1 base score is 7.5 (High), reflecting the network attack vector, low complexity, no privileges required, no user interaction, and an impact limited to availability. The vulnerability affects all versions of the listed products prior to specific patch levels or updates, which have not yet been linked in the provided data. No known exploits have been reported in the wild as of the publication date (March 12, 2024). Given the critical role of these systems in fire safety and building management, the vulnerability poses a significant operational risk if exploited.

Potential Impact

For European organizations, the impact of CVE-2024-22040 could be substantial, especially for those relying on Siemens Cerberus PRO and Sinteso fire safety systems in commercial buildings, industrial sites, hospitals, and critical infrastructure. A successful exploitation would cause denial of service by crashing the network communication service of these devices, potentially disabling fire detection, alarm signaling, and emergency response coordination. This could lead to delayed incident detection and response, increasing safety risks and regulatory non-compliance. The disruption could also affect building management systems integrated with these fire panels, causing broader operational interruptions. While the vulnerability does not directly compromise confidentiality or integrity, the availability impact alone is critical given the safety functions involved. Additionally, the ease of remote exploitation without authentication increases the risk of opportunistic attacks or targeted disruptions by malicious actors. European organizations in sectors such as manufacturing, healthcare, transportation, and public administration are particularly vulnerable due to their reliance on these Siemens products for fire safety and compliance with stringent EU safety regulations.

Mitigation Recommendations

1. Apply vendor patches and updates as soon as they become available for all affected Siemens Cerberus PRO EN and Sinteso FS20 EN products. Monitor Siemens security advisories closely. 2. Implement network segmentation and isolate fire safety systems from general IT networks and the internet to reduce exposure to remote attacks. 3. Deploy firewall rules to restrict inbound traffic to only trusted management stations and authorized devices communicating with the fire panels. 4. Monitor network traffic for anomalous or malformed packets targeting the HMAC validation process, which could indicate exploitation attempts. 5. Use intrusion detection/prevention systems (IDS/IPS) with signatures or heuristics tuned to detect exploitation patterns related to this vulnerability. 6. Conduct regular security audits and penetration testing focused on fire safety and building management systems to identify and remediate weaknesses. 7. Develop and test incident response plans that include scenarios involving denial of service on fire safety systems to ensure rapid recovery and safety continuity. 8. Engage with Siemens support and cybersecurity teams for guidance and to report any suspicious activity or exploitation attempts. 9. Consider deploying redundant fire safety systems or failover mechanisms to maintain availability in case of service disruption.

Need more detailed analysis?Upgrade to Pro Console

Technical Details

Data Version
5.2
Assigner Short Name
siemens
Date Reserved
2024-01-04T13:24:07.552Z
Cvss Version
3.1
State
PUBLISHED

Threat ID: 69418d789050fe8508ffbf57

Added to database: 12/16/2025, 4:48:56 PM

Last enriched: 12/23/2025, 5:13:30 PM

Last updated: 2/7/2026, 6:36:32 PM

Views: 28

Community Reviews

0 reviews

Crowdsource mitigation strategies, share intel context, and vote on the most helpful responses. Sign in to add your voice and help keep defenders ahead.

Sort by
Loading community insights…

Want to contribute mitigation steps or threat intel context? Sign in or create an account to join the community discussion.

Actions

PRO

Updates to AI analysis require Pro Console access. Upgrade inside Console → Billing.

Please log in to the Console to use AI analysis features.

Need more coverage?

Upgrade to Pro Console in Console -> Billing for AI refresh and higher limits.

For incident response and remediation, OffSeq services can help resolve threats faster.

Latest Threats