CVE-2025-40771: CWE-306: Missing Authentication for Critical Function in Siemens SIMATIC CP 1542SP-1

0
Critical
VulnerabilityCVE-2025-40771cvecve-2025-40771cwe-306
Published: Tue Oct 14 2025 (10/14/2025, 09:15:17 UTC)
Source: CVE Database V5
Vendor/Project: Siemens
Product: SIMATIC CP 1542SP-1

Description

A vulnerability has been identified in SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.4.24). Affected devices do not properly authenticate configuration connections. This could allow an unauthenticated remote attacker to access the configuration data.

AI-Powered Analysis

AILast updated: 10/14/2025, 09:37:29 UTC

Technical Analysis

CVE-2025-40771 is a vulnerability classified under CWE-306 (Missing Authentication for Critical Function) affecting multiple Siemens SIMATIC CP 1542SP-1 and CP 1543SP-1 models, including SIPLUS variants, all versions prior to 2.4.24. These devices serve as communication processors in industrial automation environments, facilitating data exchange between controllers and networks. The vulnerability arises because the affected devices do not properly authenticate configuration connections, meaning an attacker can remotely connect to the device's configuration interface without any credentials. This lack of authentication allows unauthorized access to sensitive configuration data, which could be read or altered. Given the critical role these devices play in industrial control systems (ICS), unauthorized configuration changes could disrupt industrial processes, cause data leakage, or enable further attacks on the ICS environment. The CVSS v3.1 base score of 9.8 reflects the vulnerability's network attack vector (AV:N), low attack complexity (AC:L), no privileges required (PR:N), no user interaction (UI:N), and high impact on confidentiality (C:H), integrity (I:H), and availability (A:H). Although no exploits are currently known in the wild, the vulnerability's characteristics make it highly exploitable and dangerous. Siemens has reserved the CVE and published the vulnerability details on 2025-10-14 but has not yet provided patch links, indicating that remediation may be pending or in progress. The vulnerability affects a broad range of Siemens industrial communication processors used globally, especially in critical infrastructure and manufacturing sectors.

Potential Impact

For European organizations, the impact of CVE-2025-40771 is substantial due to the widespread use of Siemens SIMATIC CP 1542SP-1 and related devices in industrial automation and critical infrastructure sectors such as energy, manufacturing, transportation, and utilities. Unauthorized access to configuration data can lead to manipulation of industrial processes, resulting in operational disruptions, safety hazards, and potential physical damage. Confidentiality breaches could expose sensitive operational data or intellectual property, while integrity compromises could allow attackers to alter control logic or network configurations, potentially causing unsafe conditions or production downtime. Availability impacts could arise if attackers disrupt communication between controllers and networks, halting industrial operations. Given the critical nature of these systems, exploitation could have cascading effects on supply chains and national infrastructure resilience. The vulnerability's remote and unauthenticated exploitation vector increases the risk of widespread attacks, especially if threat actors develop exploits. European organizations with interconnected ICS networks and insufficient segmentation are particularly vulnerable. The absence of known exploits currently provides a window for proactive mitigation, but the critical severity demands urgent attention.

Mitigation Recommendations

1. Immediate upgrade of all affected Siemens SIMATIC CP 1542SP-1 and CP 1543SP-1 devices to firmware version 2.4.24 or later once available from Siemens. 2. Until patches are applied, implement strict network segmentation and access controls to isolate affected devices from untrusted networks and limit configuration interface access to authorized personnel only. 3. Deploy industrial intrusion detection systems (IDS) and monitoring solutions to detect unauthorized configuration connection attempts or anomalous network traffic targeting these devices. 4. Enforce strong network-level authentication mechanisms such as VPNs or jump hosts for remote access to ICS networks containing these devices. 5. Conduct thorough audits of device configurations and logs to identify any unauthorized changes or access attempts. 6. Engage with Siemens support and subscribe to their security advisories for timely updates and patches. 7. Train ICS security teams on the specifics of this vulnerability and incident response procedures tailored to configuration interface compromises. 8. Review and update ICS security policies to include authentication requirements for all critical functions and interfaces, minimizing the risk of similar vulnerabilities.

Need more detailed analysis?Get Pro

Technical Details

Data Version
5.1
Assigner Short Name
siemens
Date Reserved
2025-04-16T08:39:30.033Z
Cvss Version
3.1
State
PUBLISHED

Threat ID: 68ee16317eab8b438c025d5c

Added to database: 10/14/2025, 9:21:53 AM

Last enriched: 10/14/2025, 9:37:29 AM

Last updated: 10/16/2025, 1:21:11 PM

Views: 61

Community Reviews

0 reviews

Crowdsource mitigation strategies, share intel context, and vote on the most helpful responses. Sign in to add your voice and help keep defenders ahead.

Sort by
Loading community insights…

Want to contribute mitigation steps or threat intel context? Sign in or create an account to join the community discussion.

Actions

PRO

Updates to AI analysis require Pro Console access. Upgrade inside Console → Billing.

Please log in to the Console to use AI analysis features.

Need enhanced features?

Contact root@offseq.com for Pro access with improved analysis and higher rate limits.

Latest Threats