Skip to main content
VulnerabilityPublished

CVE-2025-40771: Siemens SIMATIC CP 1542SP-1 · Missing Authentication

Affects Siemens SIMATIC CP 1542SP-1Source CVE Database V5

0

Not known to be exploited · CVSS 9.8 Critical.

Data as of 26 Oct 2026, 11:07 UTC

CVSS 3.1 base score
9.8Critical
How severe the flaw is on the 0–10 CVSS scale.
EPSS
0.5% chance of exploitation in 30 days – higher than 44% of CVEsExploit Prediction Scoring System: the likelihood attackers will use this flaw soon.
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Exploitation evidence

  1. Disclosed: evidence found.

    CVE published 14 Oct 2025

  2. Detectable: no evidence on record.

    No public nuclei template indexed

  3. Weaponised: no evidence on record.

    No public exploit code indexed in Metasploit or Exploit-DB

  4. Exploited in the wild: no evidence on record.

    Not in CISA KEV and no source reports exploitation

  5. Observed by OffSeq Mirage: no evidence on record.

    No attack traffic recorded by OffSeq Mirage sensors

A missing step is not evidence of safety. Sources: cve.org (opens in a new tab), the Metasploit, Exploit-DB and nuclei-templates index as of 26 Oct 2026.

What to do

Affected software

ProductAffectedFixed in
Siemens SIMATIC CP 1542SP-1Affected
  • =0
Fixed in–

AI-suggested

  1. Immediately upgrade all affected Siemens SIMATIC CP 1542SP-1 and related devices to firmware version 2.4.24 or later once Siemens releases the patch.
  2. Until patches are applied, implement strict network segmentation to isolate these devices from untrusted networks and limit access to trusted management stations only.
  3. Employ firewall rules and access control lists (ACLs) to restrict configuration port access to authorized IP addresses.
  4. Monitor network traffic for unusual connection attempts to the configuration interfaces of these devices.
  5. Use industrial intrusion detection systems (IDS) tailored to detect unauthorized configuration access attempts.
  6. Conduct regular audits of device configurations and logs to detect unauthorized changes.
  7. Engage with Siemens support for any interim mitigation guidance or firmware updates.
  8. Incorporate this vulnerability into incident response plans specific to industrial control systems to ensure rapid containment if exploited.

Description

A vulnerability has been identified in SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.4.24), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.4.24), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.4.24). Affected devices do not properly authenticate configuration connections. This could allow an unauthenticated remote attacker to access the configuration data.