Skip to main content
Press slash or control plus K to focus the search. Use the arrow keys to navigate results and press enter to open a threat.
Reconnecting to live updates…

CVE-2025-9282: CWE-400 Uncontrolled Resource Consumption in Rockwell Automation ArmorStart® LT

0
High
VulnerabilityCVE-2025-9282cvecve-2025-9282cwe-400
Published: Tue Jan 20 2026 (01/20/2026, 13:59:14 UTC)
Source: CVE Database V5
Vendor/Project: Rockwell Automation
Product: ArmorStart® LT

Description

CVE-2025-9282 is a high-severity vulnerability in Rockwell Automation's ArmorStart® LT (version V2. 002 and below) that causes uncontrolled resource consumption leading to denial-of-service (DoS). Specifically, during Achilles Comprehensive limited storm tests, the device unexpectedly reboots, causing the Link State Monitor to be unavailable for several seconds. This vulnerability requires no authentication or user interaction and can be exploited remotely over the network. The impact is primarily availability-related, potentially disrupting industrial control systems relying on ArmorStart® LT. No known exploits are currently in the wild, but the high CVSS score (8. 7) indicates significant risk. European organizations using this product in critical infrastructure or manufacturing sectors should prioritize patching once available and implement network segmentation and monitoring to mitigate potential attacks. Countries with strong industrial automation sectors and critical infrastructure reliance on Rockwell Automation products, such as Germany, France, Italy, and the UK, are most likely to be affected.

AI-Powered Analysis

AILast updated: 01/20/2026, 14:35:47 UTC

Technical Analysis

CVE-2025-9282 is a vulnerability classified under CWE-400 (Uncontrolled Resource Consumption) affecting Rockwell Automation's ArmorStart® LT product, specifically versions V2.002 and earlier. The flaw manifests during the execution of Achilles Comprehensive limited storm tests, which are designed to simulate network stress conditions. Under these test conditions, the device unexpectedly reboots, causing a temporary outage of the Link State Monitor component for several seconds. This behavior indicates that the device cannot handle certain resource-intensive network events properly, leading to a denial-of-service condition. The vulnerability is remotely exploitable without requiring authentication or user interaction, making it accessible to attackers with network access to the device. The CVSS 4.0 base score of 8.7 reflects a high severity due to the network attack vector, low attack complexity, and the significant impact on availability (denial of service). The vulnerability does not affect confidentiality or integrity directly but can disrupt industrial control processes relying on ArmorStart® LT for network connectivity and monitoring. No patches or mitigations have been officially released at the time of publication, and no known exploits are reported in the wild. However, the potential for disruption in industrial environments is considerable, especially in sectors where ArmorStart® LT devices are deployed as part of critical infrastructure or manufacturing automation systems.

Potential Impact

The primary impact of CVE-2025-9282 is a denial-of-service condition caused by unexpected device reboots under specific network stress tests. For European organizations, especially those in manufacturing, energy, utilities, and critical infrastructure sectors that rely on Rockwell Automation's ArmorStart® LT devices, this vulnerability could lead to temporary network outages and loss of monitoring capabilities. Such disruptions can affect operational continuity, safety systems, and production efficiency. The Link State Monitor downtime may delay detection of network issues, increasing the risk of cascading failures or prolonged outages. Given the device's role in industrial control networks, the vulnerability could indirectly impact physical processes and safety. The lack of authentication requirements and ease of exploitation over the network raise concerns about potential targeted attacks or accidental triggers during network testing or scanning activities. Although no exploits are currently known in the wild, the high CVSS score and potential for widespread impact necessitate proactive risk management in European industrial environments.

Mitigation Recommendations

1. Implement strict network segmentation to isolate ArmorStart® LT devices from untrusted networks and limit exposure to potential attackers. 2. Monitor network traffic for unusual patterns or storm-like conditions that could trigger the vulnerability, using industrial network monitoring tools. 3. Restrict access to the devices to authorized personnel and systems only, employing access control lists and network firewalls. 4. Avoid running Achilles Comprehensive limited storm tests or similar stress tests on production devices until patches are available. 5. Engage with Rockwell Automation for updates on patches or firmware upgrades addressing CVE-2025-9282 and apply them promptly once released. 6. Develop and test incident response plans to quickly detect and recover from device reboots or network outages caused by this vulnerability. 7. Consider deploying redundant network monitoring and control systems to maintain operational continuity during device downtime. 8. Conduct regular security assessments and vulnerability scans focused on industrial control systems to identify and remediate similar risks.

Need more detailed analysis?Upgrade to Pro Console

Technical Details

Data Version
5.2
Assigner Short Name
Rockwell
Date Reserved
2025-08-20T19:46:27.783Z
Cvss Version
4.0
State
PUBLISHED

Threat ID: 696f8f574623b1157c38995a

Added to database: 1/20/2026, 2:21:11 PM

Last enriched: 1/20/2026, 2:35:47 PM

Last updated: 1/20/2026, 3:44:53 PM

Views: 5

Community Reviews

0 reviews

Crowdsource mitigation strategies, share intel context, and vote on the most helpful responses. Sign in to add your voice and help keep defenders ahead.

Sort by
Loading community insights…

Want to contribute mitigation steps or threat intel context? Sign in or create an account to join the community discussion.

Actions

PRO

Updates to AI analysis require Pro Console access. Upgrade inside Console → Billing.

Please log in to the Console to use AI analysis features.

Need more coverage?

Upgrade to Pro Console in Console -> Billing for AI refresh and higher limits.

For incident response and remediation, OffSeq services can help resolve threats faster.

Latest Threats