Skip to main content
Press slash or control plus K to focus the search. Use the arrow keys to navigate results and press enter to open a threat.
Reconnecting to live updates…

CVE-2024-32009: CWE-266: Incorrect Privilege Assignment in Siemens Spectrum Power 4

0
High
VulnerabilityCVE-2024-32009cvecve-2024-32009cwe-266
Published: Tue Nov 11 2025 (11/11/2025, 20:20:15 UTC)
Source: CVE Database V5
Vendor/Project: Siemens
Product: Spectrum Power 4

Description

A vulnerability has been identified in Spectrum Power 4 (All versions < V4.70 SP12 Update 2). The affected application is vulnerable to a local privilege escalation due to wrongly set permissions to a binary which allows any local attacker to gain administrative privileges.

AI-Powered Analysis

AILast updated: 11/18/2025, 22:35:20 UTC

Technical Analysis

CVE-2024-32009 is a vulnerability classified under CWE-266 (Incorrect Privilege Assignment) affecting Siemens Spectrum Power 4, a widely used energy management and distribution software platform. The flaw exists in the permissions set on a specific binary within the application, which are overly permissive and allow any local user to execute the binary with administrative privileges. This misconfiguration enables a local attacker to escalate their privileges from a limited user to an administrator without requiring user interaction or complex attack vectors. The vulnerability affects all versions of Spectrum Power 4 prior to V4.70 SP12 Update 2. The CVSS v3.1 base score is 7.8, indicating a high severity due to the combination of local attack vector, low attack complexity, required privileges being low, and no user interaction needed. The impact on confidentiality, integrity, and availability is high because administrative privileges grant full control over the system and potentially the energy management environment. Although no exploits have been publicly reported, the vulnerability poses a significant risk to organizations relying on Spectrum Power 4 for critical infrastructure management. Siemens has not yet published patches but the vendor is expected to release updates to remediate the issue. The vulnerability highlights the importance of secure permission management on binaries in critical industrial control software.

Potential Impact

For European organizations, especially those operating critical energy infrastructure, this vulnerability could lead to severe consequences. An attacker gaining administrative privileges locally could manipulate energy distribution controls, disrupt service availability, or exfiltrate sensitive operational data. This could result in operational downtime, financial losses, regulatory penalties, and damage to national critical infrastructure resilience. Since Spectrum Power 4 is used in energy management, the impact extends to grid stability and public safety. The vulnerability’s local nature means that attackers must have some initial access, but insider threats or compromised local accounts could exploit this flaw easily. The high integrity and availability impact could lead to cascading failures in energy supply chains. European energy operators must consider this vulnerability a high priority due to the strategic importance of energy infrastructure and the potential for targeted attacks.

Mitigation Recommendations

1. Immediately restrict local access to systems running Spectrum Power 4 to trusted and authenticated personnel only. 2. Monitor and audit local user activities for unusual privilege escalation attempts or binary executions. 3. Apply the official Siemens patch or update to Spectrum Power 4 as soon as it becomes available (V4.70 SP12 Update 2 or later). 4. In the interim, manually review and correct file system permissions on the vulnerable binary to ensure it is not executable by unauthorized users. 5. Employ endpoint detection and response (EDR) tools to detect anomalous local privilege escalation behaviors. 6. Harden local user accounts by enforcing least privilege principles and disabling unnecessary accounts. 7. Conduct regular security training for administrators and operators on the risks of local privilege escalation. 8. Implement network segmentation to limit lateral movement if a local account is compromised. 9. Maintain up-to-date backups and incident response plans tailored for industrial control systems. 10. Collaborate with Siemens support and follow advisories for any additional recommended mitigations.

Need more detailed analysis?Get Pro

Technical Details

Data Version
5.2
Assigner Short Name
siemens
Date Reserved
2024-04-08T15:37:27.222Z
Cvss Version
3.1
State
PUBLISHED

Threat ID: 6913a08bf4d5bbdab5b1c72b

Added to database: 11/11/2025, 8:46:03 PM

Last enriched: 11/18/2025, 10:35:20 PM

Last updated: 11/22/2025, 3:17:28 PM

Views: 30

Community Reviews

0 reviews

Crowdsource mitigation strategies, share intel context, and vote on the most helpful responses. Sign in to add your voice and help keep defenders ahead.

Sort by
Loading community insights…

Want to contribute mitigation steps or threat intel context? Sign in or create an account to join the community discussion.

Actions

PRO

Updates to AI analysis require Pro Console access. Upgrade inside Console → Billing.

Please log in to the Console to use AI analysis features.

Need enhanced features?

Contact root@offseq.com for Pro access with improved analysis and higher rate limits.

Latest Threats