Skip to main content
Press slash or control plus K to focus the search. Use the arrow keys to navigate results and press enter to open a threat.
Reconnecting to live updates…

CVE-2023-33919: CWE-77: Improper Neutralization of Special Elements used in a Command ('Command Injection') in Siemens CP-8031 MASTER MODULE

0
High
VulnerabilityCVE-2023-33919cvecve-2023-33919cwe-77
Published: Tue Jun 13 2023 (06/13/2023, 08:17:18 UTC)
Source: CVE Database V5
Vendor/Project: Siemens
Product: CP-8031 MASTER MODULE

Description

A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). The web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated privileged remote attacker to execute arbitrary code with root privileges.

AI-Powered Analysis

AILast updated: 11/03/2025, 22:04:14 UTC

Technical Analysis

CVE-2023-33919 is a command injection vulnerability classified under CWE-77 that affects Siemens CP-8031 and CP-8050 MASTER MODULE devices running firmware versions earlier than CPCI85 V05. The root cause is the absence of proper server-side input validation in the web interface, which allows specially crafted input to be executed as system commands. An attacker with authenticated privileged access to the web interface can exploit this flaw to execute arbitrary code with root privileges, potentially taking full control of the device. The vulnerability does not require user interaction but does require high privilege authentication, which limits exposure but still presents a significant risk in environments where credentials could be compromised or insider threats exist. The impact includes full compromise of the device, enabling attackers to manipulate industrial communication processes, disrupt operations, or pivot into other network segments. Siemens has published the vulnerability with a CVSS v3.1 base score of 7.2, indicating high severity. No public exploits or active exploitation have been reported yet. The vulnerability affects all versions prior to CPCI85 V05, and Siemens recommends upgrading to the fixed firmware version to remediate the issue. Given the critical role these modules play in industrial automation and control systems, exploitation could have severe operational consequences.

Potential Impact

For European organizations, particularly those in manufacturing, energy, utilities, and critical infrastructure sectors, this vulnerability poses a substantial risk. Successful exploitation can lead to full device compromise, allowing attackers to manipulate industrial processes, cause operational downtime, or disrupt supply chains. The root-level access gained through this vulnerability could also facilitate lateral movement within industrial control networks, potentially affecting broader operational technology (OT) environments. Confidentiality of sensitive operational data could be breached, integrity of control commands compromised, and availability of critical systems disrupted. Given the strategic importance of industrial automation in Europe’s economy and infrastructure, the impact could extend beyond individual organizations to national critical infrastructure. The requirement for privileged authentication reduces the attack surface but does not eliminate risk, especially in scenarios involving credential theft or insider threats.

Mitigation Recommendations

1. Immediately upgrade affected Siemens CP-8031 and CP-8050 MASTER MODULE devices to firmware version CPCI85 V05 or later, where the vulnerability is patched. 2. Restrict access to the web management interface using network segmentation, firewall rules, and VPNs to limit exposure to trusted administrators only. 3. Enforce strong authentication mechanisms, including multi-factor authentication (MFA), to reduce the risk of credential compromise. 4. Regularly audit and monitor access logs for anomalous or unauthorized access attempts to the device interfaces. 5. Implement strict credential management policies, including regular password changes and least privilege principles for administrative accounts. 6. Conduct periodic vulnerability assessments and penetration testing focused on industrial control systems to detect similar issues proactively. 7. Maintain an incident response plan tailored to industrial control system compromises to quickly contain and remediate potential exploitation.

Need more detailed analysis?Get Pro

Technical Details

Data Version
5.2
Assigner Short Name
siemens
Date Reserved
2023-05-23T10:09:31.037Z
Cvss Version
3.1
State
PUBLISHED

Threat ID: 69092143fe7723195e053f16

Added to database: 11/3/2025, 9:40:19 PM

Last enriched: 11/3/2025, 10:04:14 PM

Last updated: 11/6/2025, 1:16:55 PM

Views: 3

Community Reviews

0 reviews

Crowdsource mitigation strategies, share intel context, and vote on the most helpful responses. Sign in to add your voice and help keep defenders ahead.

Sort by
Loading community insights…

Want to contribute mitigation steps or threat intel context? Sign in or create an account to join the community discussion.

Actions

PRO

Updates to AI analysis require Pro Console access. Upgrade inside Console → Billing.

Please log in to the Console to use AI analysis features.