CVE-2025-41714: CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') in Welotec SmartEMS Web Application
The upload endpoint insufficiently validates the 'Upload-Key' request header. By supplying path traversal sequences, an authenticated attacker can cause the server to create upload-related artifacts outside the intended storage location. In certain configurations this enables arbitrary file write and may be leveraged to achieve remote code execution.
AI Analysis
Technical Summary
CVE-2025-41714 is a high-severity vulnerability classified under CWE-22, which pertains to improper limitation of a pathname to a restricted directory, commonly known as a path traversal flaw. This vulnerability affects the Welotec SmartEMS Web Application, specifically its upload endpoint. The core issue lies in insufficient validation of the 'Upload-Key' HTTP request header. An authenticated attacker can manipulate this header by injecting path traversal sequences (e.g., '../') to cause the server to write upload-related files outside the intended directory. Depending on the server configuration, this can lead to arbitrary file write capabilities. Such unauthorized file writes can be leveraged to place malicious files or scripts on the server, potentially enabling remote code execution (RCE). The vulnerability requires the attacker to have some level of authentication (PR:L - privileges required), but does not require user interaction (UI:N). The CVSS 3.1 base score of 8.8 reflects the high impact on confidentiality, integrity, and availability, as successful exploitation can compromise the entire system. No public exploits are currently known in the wild, and no patches have been linked yet. The vulnerability was published on September 10, 2025, with the initial reservation date in April 2025. The affected version is listed as v0.0.0, which likely indicates the initial or a specific early release of the SmartEMS Web Application. This vulnerability is critical for environments where Welotec SmartEMS is deployed, especially in industrial or energy management contexts where SmartEMS is typically used.
Potential Impact
For European organizations using Welotec SmartEMS, this vulnerability poses a significant risk. Successful exploitation can lead to unauthorized access and control over critical energy management systems, potentially disrupting operations, causing data breaches, or enabling sabotage. The arbitrary file write and possible remote code execution could allow attackers to implant backdoors, manipulate energy distribution data, or cause denial of service by corrupting system files. Given the strategic importance of energy infrastructure in Europe, such compromises could have cascading effects on national grids, industrial facilities, and critical services. Confidentiality breaches could expose sensitive operational data, while integrity violations could lead to incorrect energy management decisions. Availability impacts could result in outages or degraded service. The requirement for authentication limits exposure somewhat but does not eliminate risk, especially if credentials are compromised or insider threats exist. The lack of known exploits in the wild suggests a window for proactive mitigation before widespread attacks occur.
Mitigation Recommendations
1. Immediate implementation of strict input validation and sanitization on the 'Upload-Key' header to prevent path traversal sequences. 2. Employ allowlisting of acceptable characters and patterns in the 'Upload-Key' header to restrict directory traversal attempts. 3. Enforce the use of secure, canonicalized paths when handling file uploads to ensure files are stored only within designated directories. 4. Implement robust authentication and session management to reduce the risk of credential compromise. 5. Conduct thorough code reviews and penetration testing focused on file upload functionality. 6. Monitor logs for unusual file creation patterns or access outside expected directories. 7. Segregate the upload storage area with strict filesystem permissions to limit the impact of any unauthorized writes. 8. Apply network segmentation and least privilege principles to restrict access to the SmartEMS application. 9. Prepare incident response plans specific to potential RCE scenarios in SmartEMS environments. 10. Coordinate with Welotec for timely patches and updates once available, and prioritize their deployment. 11. Consider deploying Web Application Firewalls (WAFs) with custom rules to detect and block path traversal attempts targeting the upload endpoint.
Affected Countries
Germany, France, United Kingdom, Italy, Spain, Netherlands, Belgium, Poland, Sweden, Austria
CVE-2025-41714: CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') in Welotec SmartEMS Web Application
Description
The upload endpoint insufficiently validates the 'Upload-Key' request header. By supplying path traversal sequences, an authenticated attacker can cause the server to create upload-related artifacts outside the intended storage location. In certain configurations this enables arbitrary file write and may be leveraged to achieve remote code execution.
AI-Powered Analysis
Technical Analysis
CVE-2025-41714 is a high-severity vulnerability classified under CWE-22, which pertains to improper limitation of a pathname to a restricted directory, commonly known as a path traversal flaw. This vulnerability affects the Welotec SmartEMS Web Application, specifically its upload endpoint. The core issue lies in insufficient validation of the 'Upload-Key' HTTP request header. An authenticated attacker can manipulate this header by injecting path traversal sequences (e.g., '../') to cause the server to write upload-related files outside the intended directory. Depending on the server configuration, this can lead to arbitrary file write capabilities. Such unauthorized file writes can be leveraged to place malicious files or scripts on the server, potentially enabling remote code execution (RCE). The vulnerability requires the attacker to have some level of authentication (PR:L - privileges required), but does not require user interaction (UI:N). The CVSS 3.1 base score of 8.8 reflects the high impact on confidentiality, integrity, and availability, as successful exploitation can compromise the entire system. No public exploits are currently known in the wild, and no patches have been linked yet. The vulnerability was published on September 10, 2025, with the initial reservation date in April 2025. The affected version is listed as v0.0.0, which likely indicates the initial or a specific early release of the SmartEMS Web Application. This vulnerability is critical for environments where Welotec SmartEMS is deployed, especially in industrial or energy management contexts where SmartEMS is typically used.
Potential Impact
For European organizations using Welotec SmartEMS, this vulnerability poses a significant risk. Successful exploitation can lead to unauthorized access and control over critical energy management systems, potentially disrupting operations, causing data breaches, or enabling sabotage. The arbitrary file write and possible remote code execution could allow attackers to implant backdoors, manipulate energy distribution data, or cause denial of service by corrupting system files. Given the strategic importance of energy infrastructure in Europe, such compromises could have cascading effects on national grids, industrial facilities, and critical services. Confidentiality breaches could expose sensitive operational data, while integrity violations could lead to incorrect energy management decisions. Availability impacts could result in outages or degraded service. The requirement for authentication limits exposure somewhat but does not eliminate risk, especially if credentials are compromised or insider threats exist. The lack of known exploits in the wild suggests a window for proactive mitigation before widespread attacks occur.
Mitigation Recommendations
1. Immediate implementation of strict input validation and sanitization on the 'Upload-Key' header to prevent path traversal sequences. 2. Employ allowlisting of acceptable characters and patterns in the 'Upload-Key' header to restrict directory traversal attempts. 3. Enforce the use of secure, canonicalized paths when handling file uploads to ensure files are stored only within designated directories. 4. Implement robust authentication and session management to reduce the risk of credential compromise. 5. Conduct thorough code reviews and penetration testing focused on file upload functionality. 6. Monitor logs for unusual file creation patterns or access outside expected directories. 7. Segregate the upload storage area with strict filesystem permissions to limit the impact of any unauthorized writes. 8. Apply network segmentation and least privilege principles to restrict access to the SmartEMS application. 9. Prepare incident response plans specific to potential RCE scenarios in SmartEMS environments. 10. Coordinate with Welotec for timely patches and updates once available, and prioritize their deployment. 11. Consider deploying Web Application Firewalls (WAFs) with custom rules to detect and block path traversal attempts targeting the upload endpoint.
For access to advanced analysis and higher rate limits, contact root@offseq.com
Technical Details
- Data Version
- 5.1
- Assigner Short Name
- CERTVDE
- Date Reserved
- 2025-04-16T11:17:48.311Z
- Cvss Version
- 3.1
- State
- PUBLISHED
Threat ID: 68c12201e55cc6e90d9f5602
Added to database: 9/10/2025, 7:00:17 AM
Last enriched: 9/10/2025, 7:15:16 AM
Last updated: 9/10/2025, 11:00:54 AM
Views: 8
Related Threats
CVE-2025-40725: CWE-79 Improper Neutralization of Input During Web Page Generation (XSS or 'Cross-site Scripting') in Azon Dominator Azon Dominator PHP script
MediumCVE-2025-40979: CWE-427 Uncontrolled Search Path Element in Grandstream Networks Wave
HighCVE-2025-36759: CWE-200 Exposure of Sensitive Information to an Unauthorized Actor in SolaX Power SolaX Cloud
HighCVE-2025-36758: CWE-307 Improper Restriction of Excessive Authentication Attempts in SolaX Power SolaX Cloud
MediumCVE-2025-36757: CWE-306 Missing Authentication for Critical Function in SolaX Power SolaX Cloud
MediumActions
Updates to AI analysis are available only with a Pro account. Contact root@offseq.com for access.
External Links
Need enhanced features?