A vulnerability exists in Asset Suite for an authenticated user to manipulate the content of performance related log data or to inject crafted data in logfile for potentially carrying out further malicious attacks. Performance logging is typically enabled for troubleshooting purposes while resolving application performance related issues.
A vulnerability exists in the IEC 61850 in MicroSCADA X SYS600 product. The certificate validation of the TLS protocol allows remote Man-in-the-Middle attack due to missing proper validation.
A vulnerability exists in the Web interface of the MicroSCADA X SYS600 product. The filtering query in the Web interface can be malformed, so returning data can leak unauthorized information to the user.
A vulnerability exists in the IEC 61850 of the MicroSCADA X SYS600 product. An IEC 61850-8 crafted message content from IED or remote system can cause a denial of service resulting in disconnection loop.
A vulnerability exists in in the Monitor Pro interface of the MicroSCADA X SYS600 product. An authenticated user with low privileges can see and overwrite files causing information leak and data corruption.
A vulnerability exists in MicroSCADA X SYS600 product. If exploited this could allow a local unauthenticated attacker to tamper a system file, making denial of Notify service.
A denial-of-service vulnerability due to improper prioritization of network traffic over protection mechanism exists in Relion 670/650 and SAM600-IO series device that if exploited could potentially cause critical functions like LDCM (Line Distance Communication Module) to malfunction.
An authenticated user with file access privilege via FTP access can cause the Relion 670/650 and SAM600-IO series device to reboot due to improper disk space management.
A vulnerability exists in the SOAP Web services of the Asset
Suite versions listed below. If successfully exploited, an attacker
could gain unauthorized access to the product and the time window of a possible password attack could be expanded.
A vulnerability exists in the media upload component of the Asset
Suite versions listed below. If successfully exploited an attacker
could impact the confidentiality or integrity of the system. An attacker can use this vulnerability to construct a request that will
cause JavaScript code supplied by the attacker to execute within
the user’s browser in the context of that user’s session with the
application.
A Host Header Injection vulnerability in TRMTracker application may allow an attacker by modifying the host header value in an HTTP request to leverage multiple attack vectors, including defacing the site content through web-cache poisoning.
Command injection vulnerability in the Edge Computing UI for the
TRO600 series radios that allows for the execution of arbitrary system commands. If exploited, an attacker with write access to the
web UI can execute commands on the device with root privileges,
far more extensive than what the write privilege intends.
CVE-2024-2617 is a high-severity vulnerability in Hitachi Energy's RTU500 series CMU firmware that allows authenticated and authorized users to bypass the secure update mechanism if it is not enabled on all CMUs of an RTU500 device. This flaw enables an attacker to update the device with unsigned firmware, potentially compromising its integrity and security. The vulnerability affects firmware versions 13.2.1, 13.4.1, and 13.5.1. There is no information about an available patch or vendor advisory specifying remediation.
An authenticated malicious client can send a special LINQ query
to execute arbitrary code remotely (RCE) on the SCM server
from List control, and execute the arbitrary code on the same
system where SCMArchivedEventViewerTool is installed in the
case of SCM Tools.
SCM Software is a client and server application. An Authenticated System manager client can execute LINQ query in the SCM server, for customized filtering. An Authenticated malicious client can send a specially crafted code to skip the validation and execute arbitrary code (RCE) on the SCM Server remotely. Malicious clients can execute any command by using this RCE vulnerability.
Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1.cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1.cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1.cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1.cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*