A partial string comparison vulnerability (CWE-187) exists in Siemens RUGGEDCOM RM1224 LTE(4G) EU and various SCALANCE devices before version 8.2.1 (or 3.2 for some models). The affected devices improperly validate usernames during OpenVPN authentication, potentially allowing attackers to have partial invalid usernames accepted by the server. The vulnerability has a low CVSS score of 3.7 and does not impact confidentiality or availability but may affect integrity. Siemens has released an official fix addressing this issue.
A vulnerability has been identified in Teamcenter V14.1 (All versions), Teamcenter V14.2 (All versions), Teamcenter V14.3 (All versions < V14.3.0.14), Teamcenter V2312 (All versions < V2312.0010), Teamcenter V2406 (All versions < V2406.0008), Teamcenter V2412 (All versions < V2412.0004). The SSO login service of affected applications accepts user-controlled input that could specify a link to an external site. This could allow an attacker to redirect the legitimate user to an attacker-chosen URL to steal valid session data. For a successful exploit, the legitimate user must actively click on an attacker-crafted link.
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V05.30). The affected devices contain a secure element which is connected via an unencrypted SPI bus. This could allow an attacker with physical access to the SPI bus to observe the password used for the secure element authentication, and then use the secure element as an oracle to decrypt all encrypted update files.
A vulnerability has been identified in SINEC Security Monitor (All versions < V4.9.0). The affected application does not properly validate that user input complies with a list of allowed values.
This could allow an authenticated remote attacker to compromise the integrity of the configuration of the affected application.
A vulnerability has been identified in SINEC Security Monitor (All versions < V4.9.0). The affected application does not properly validate a file path that is supplied to an endpoint intended to create CSR files.
This could allow an unauthenticated remote attacker to create files in writable directories outside the intended location and thus compromise integrity of files in those writable directories.
A vulnerability has been identified in SINEC Security Monitor (All versions < V4.9.0). The affected application does not properly neutralize special elements in user input to the ```ssmctl-client``` command.
This could allow an authenticated, lowly privileged local attacker to execute privileged commands in the underlying OS.
A vulnerability has been identified in SINEC Security Monitor (All versions < V4.9.0). The affected application does not properly validate user input to the ```ssmctl-client``` command.
This could allow an authenticated, lowly privileged remote attacker to execute arbitrary code with root privileges on the underlying OS.
A vulnerability has been identified in Omnivise T3000 Application Server R9.2 (All versions), Omnivise T3000 R8.2 SP3 (All versions), Omnivise T3000 R8.2 SP4 (All versions). The affected system exposes the port of an internal application on the public network interface allowing an attacker to circumvent authentication and directly access the exposed application.
A vulnerability has been identified in Omnivise T3000 Application Server R9.2 (All versions), Omnivise T3000 R8.2 SP3 (All versions), Omnivise T3000 R8.2 SP4 (All versions). Affected devices allow authenticated users to export diagnostics data. The corresponding API endpoint is susceptible to path traversal and could allow an authenticated attacker to download arbitrary files from the file system.
A vulnerability has been identified in Omnivise T3000 Application Server R9.2 (All versions), Omnivise T3000 Domain Controller R9.2 (All versions), Omnivise T3000 Network Intrusion Detection System (NIDS) R9.2 (All versions), Omnivise T3000 Product Data Management (PDM) R9.2 (All versions), Omnivise T3000 R8.2 SP3 (All versions), Omnivise T3000 R8.2 SP4 (All versions), Omnivise T3000 Security Server R9.2 (All versions), Omnivise T3000 Terminal Server R9.2 (All versions), Omnivise T3000 Thin Client R9.2 (All versions), Omnivise T3000 Whitelisting Server R9.2 (All versions). The affected devices stores initial system credentials without sufficient protection. An attacker with remote shell access or physical access could retrieve the credentials leading to confidentiality loss allowing the attacker to laterally move within the affected network.
A vulnerability has been identified in Omnivise T3000 Application Server R9.2 (All versions), Omnivise T3000 Domain Controller R9.2 (All versions), Omnivise T3000 Product Data Management (PDM) R9.2 (All versions), Omnivise T3000 R8.2 SP3 (All versions), Omnivise T3000 R8.2 SP4 (All versions), Omnivise T3000 Terminal Server R9.2 (All versions), Omnivise T3000 Thin Client R9.2 (All versions), Omnivise T3000 Whitelisting Server R9.2 (All versions). The affected application regularly executes user modifiable code as a privileged user. This could allow a local authenticated attacker to execute arbitrary code with elevated privileges.
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V5.40), SICORE Base system (All versions < V1.4.0). Affected devices allow a remote authenticated user or an unauthenticated user with physical access to downgrade the firmware of the device. This could allow an attacker to downgrade the device to older versions with known vulnerabilities.